Monitoring and maintenance

Fronius errors 102, 103 and 107 (and 1063, 1119 and 1256 on GEN24): grid out of limits, with two real cases

What Fronius grid state codes mean (102 high voltage, 103 low voltage, 105 and 106 frequency, 107 no grid; 1063, 1114, 1119 and 1256 on GEN24), why they almost always clear by themselves, when they point to a fault in the installation and how to find out what they cost. With two real cases from Madrid.

By Suntropy · Updated · Markdown

In short

They are grid state codes. 102 means the AC voltage is too high, 103 too low, 105 and 106 frequency too high or too low, and 107 that the inverter cannot detect the grid. On Fronius GEN24 inverters the same family shows up as 1063, 1114, 1119 and 1256. They are temporary errors: the inverter disconnects and only resumes exporting when the grid is back within the country limits. If they repeat every day, leave the inverter off for hours or only affect one plant and not others in the area, measure the voltage at the AC terminals and check the wiring, protection devices and the country setup. You can connect your Fronius Solar.web plants to Suntropy Connect and Alexandria tells you what each alarm cost by comparing with nearby plants: https://www.suntropy.ai/en/alexandria/mantenimiento/

  • Fronius codes 102 to 107 (Primo, Symo, Galvo) are grid errors: voltage too high (102) or too low (103), frequency too high (105) or too low (106) and no AC grid (107). On GEN24 inverters the same family shows up as 1063 («AC grid conditions out of feed-in limits»), 1114 and 1119 (voltage too high and too low) and 1256 («No feedback of the interlock relay»).
  • Fronius classes them as class 1 errors, usually temporary and caused by the public grid: the inverter disconnects, monitors the grid and starts exporting again by itself once it is back within limits.
  • In both real cases in this article, the alarms were still open in Solar.web days later even though the inverters were producing normally. One lost almost nothing; the other lost about two hours of one morning, around 0.6 kWh.
  • You need to act if it repeats every day at the same time, if the inverter stays off for hours or if it only happens on that plant and not on others in the area: then the problem is usually in the installation (AC wiring or protection devices, one phase, the country setup) and not in the grid.

Grid errors are the Fronius state codes that raise the most alarms in Solar.web and the ones that should trigger the fewest site visits. The inverter measures grid voltage and frequency before connecting and while exporting; if they go outside the country limits, it disconnects, logs it and reconnects by itself once the grid is back to normal. The problem is that the alarm stays open in the portal and, on its own, it does not tell you whether the inverter was off for five minutes or all morning.

This article uses two real cases from this week, two homes in the Madrid region (Spain) with Fronius inverters. The data are the ones in Fronius Solar.web, read through Suntropy Connect, which is where Alexandria gets them. We removed names and addresses; production figures and times are the original ones.

What each code means

Fronius Primo, Symo and Galvo (three-digit codes):

CodeWhat it indicates
102AC voltage too high
103AC voltage too low
105Grid frequency too high
106Grid frequency too low
107No AC grid detected (in some editions of the manual, «grid outside tolerances»)

Fronius GEN24 and GEN24 Plus (four-digit codes):

CodeWhat it indicates
1063AC grid conditions out of feed-in limits
1114AC voltage too high
1119AC voltage too low
1256No feedback of the interlock relay (the relay that connects the inverter to the grid does not confirm its state)

The limits are not fixed: they depend on the country setup chosen when the inverter was commissioned. The Primo manual gives 230 V with a tolerance of +10 % / -5 % as a reference, depending on the country.

Fronius classes 102 to 107 as class 1 errors, which are generally temporary and come from the public grid. The expected behaviour is that the inverter disconnects, checks the grid and resumes exporting by itself.

Case 1: a GEN24 with three alarms in a row that cost nothing

Home in the west of the Madrid region: 6.3 kWp, Primo GEN24 6.0 Plus inverter with battery, in service since 2021. On the afternoon of Monday 16 November, Solar.web logged three alarms in an hour and a half:

TimeCodeText in Solar.web
14:441063AC grid conditions out of feed-in limits
14:501256No feedback of the interlock relay
16:201119AC voltage too low

Read like that, it looks like a relay or grid fault. The hourly curve for that day says otherwise:

HourProduction
12:00-13:000.91 kWh
13:00-14:001.84 kWh
14:00-15:002.50 kWh
15:00-16:002.19 kWh
16:00-17:000.62 kWh
17:00-18:000.16 kWh

The hour of the first two alarms was the best of the day. The drop at 16:00 is the same as any November afternoon: the next day, with no alarms, the same slot gave 0.58 kWh. Monday ended at 10.2 kWh, the second-best day of the week. The outages, if there were any, lasted minutes.

Diagnosis: a grid disturbance lasting a few minutes. The inverter disconnected, the relay was slow to confirm and it reconnected by itself. Nothing to do, other than watching whether it repeats. And yet the three alarms were still open in Solar.web two days later.

Case 2: a Symo that did not see the grid all morning

Home in the city of Madrid: 6.05 kWp, three-phase Symo 6.0-3-M inverter, in service since May 2026. On Tuesday 17 November:

  • 8:58 — 103 «AC voltage too low».
  • 9:04 — 107 «No AC grid detected».

Hourly production, compared with the plant from case 1, about 15 km away:

HourThis plant (6.05 kWp)Case 1 plant (6.3 kWp)
8:00-9:0000.08 kWh
9:00-10:0000.19 kWh
10:00-11:0000.31 kWh
11:00-12:000.74 kWh0.41 kWh
12:00-13:000.81 kWh1.13 kWh
13:00-14:000.82 kWh0.90 kWh

Here there was a real stop: from 8:00 to 11:00 the inverter did not export while the nearby plant was already producing. From 11:00 it started up and the afternoon was normal. Adjusted for size, the lost morning is about 0.6 kWh. The day ended at 3.6 kWh, in the same ratio to the case 1 plant as the rest of the week.

Diagnosis: the inverter could not see the AC grid, or saw it with the voltage below the limit, first thing in the morning. On a three-phase inverter, a 103 followed by a 107 points to a low or missing phase at start-up. It could be the grid (an incident on the distribution network that morning) or the installation (a protection device, a loose terminal on one phase). Once does not say much; if it repeats every morning, you need to measure.

When it is the grid and when it is the installation

What you seeMost likely causeWhat to do
A single grid alarm, and the day's production is normalA grid disturbance lasting minutesNothing. Watch whether it repeats
The same alarm on several plants in the area on the same dayThe distribution networkNothing on the plants. If it happens a lot, file a complaint with the grid operator using the Solar.web times
102 or 1114 in the sunniest hours, day after dayVoltage rises when exporting: a long or undersized line to the meter, or a weak gridMeasure the voltage at the terminals with the inverter exporting, and the voltage drop on the AC cable
103, 107 or 1119 every morning at the same time, only on that plantA low or missing phase, a protection device or a loose terminalSite visit: measure the voltage per phase at the terminals and check AC protection devices and connections
The inverter stays off for hours with the alarmThe grid does not return within limits or there is a fault on the AC sideSite visit
1256 repeating even though the grid is fineThe inverter's interlock relayFronius technical support
Grid alarms since commissioningWrong country setup or outdated firmwareCheck the country setup and update the firmware

One question for the customer before going out: «Have you noticed power cuts or flickering lights at home on those days?» If yes, it is the grid and a site visit will not fix anything.

Why looking at the alarm is not enough

In both cases, the alarms were still open in Solar.web days later, with the inverters producing. With dozens of plants, that means an inbox full of red alarms where the one that matters (case 2, if it repeats) gets lost among the ones that don't (case 1). To tell them apart you have to cross-check the alarm, the hourly curve and the production of plants in the area.

If you are an AI agent: how to repeat this diagnosis

  1. With list_alarms (provider: fronius), find the grid alarms: codes 102, 103, 105, 106, 107, 1063, 1114, 1119 and 1256, with their plantId and raisedAt.
  2. Call get_plant_energy with metric: pv_yield and granularity: hour for the day of the alarm. If production in the following hours is normal, the outage lasted minutes.
  3. Use list_plants to find one or two nearby plants and request their hourly production for the same day. The hours at zero on the plant and not on its neighbour are what the alarm cost.
  4. With list_alarms over the last 30 days, check whether the same alarm repeats at the same time. Daily repetition on a single plant means the installation; on several plants, the grid.
  5. Say whether it reconnected by itself, how much was lost and whether to keep an eye on it or send a technician, following the table above.

Frequently asked questions

What does Fronius error 102 mean?

That the AC voltage exceeds the limit of the country setup. The inverter stops exporting until it drops. If it appears in the hours of highest production and repeats every day, it is usually caused by the voltage rise produced by the export itself on a long or undersized line.

What does Fronius error 107 mean?

That the inverter cannot detect the AC grid (or, according to the manual, that it is outside tolerances). It usually appears during grid outages or when a phase is missing. If the inverter reconnects by itself, there is nothing to do; if it stays off, check the protection devices and the voltage at the terminals.

What is code 1063 on a Fronius GEN24?

It is the warning that grid conditions (voltage or frequency) are outside the feed-in limits. It is the GEN24 equivalent of the 102-107 family: the inverter disconnects and resumes exporting when the grid returns to normal.

And 1256 «No feedback of the interlock relay»?

It means the relay that connects the inverter to the grid has not confirmed its state. It usually appears together with other grid alarms, as in case 1, and clears on reconnection. If it repeats with the grid in good condition, it is a job for Fronius technical support.

Can the inverter's voltage limit be changed?

The limits come from the country setup and the grid connection rules, and only authorised personnel can change them. Before touching the limits, measure: if the voltage rises because of the drop along the AC cable, the fix is the line, not the setting.

The alarm is still open in Solar.web: is the inverter off?

Not necessarily. In both cases in this article the alarms were still open days later with the inverters producing. Look at the hourly production: if it is normal, the alarm is over.

Sources

  • Alarms, daily and hourly production and devices from the Fronius Solar.web platform for the two installations in the cases (8 to 18 November 2026), read with Suntropy Connect.
  • Fronius Primo operating instructions, table of class 1 state codes (102, 103, 105, 106 and 107) and voltage tolerance.
  • Fronius Primo/Symo GEN24 operating instructions, table of state codes (1114 and 1119).
  • Fronius, GEN24 state codes support page: https://www.fronius.com/en/solar-energy/home-owners/contact/support-for-pv-system-owners/support-state-codes-gen24