Monitoring and maintenance
«Inefficient Power Plants» in SolisCloud: how to tell if the warning is real (two real plants)
What the «Inefficient Power Plants» warning in SolisCloud means, why it stays open for months, and how to tell a false positive from a real loss by comparing production per kWp month by month. With two real plants: one healthy and one that loses 80 % in winter.
In short
It is a statistical warning from SolisCloud (code 1D4C3) estimating that the plant produces less than expected; it is not an inverter alarm and it can be a false positive. You check it by comparing production per kWp month by month with a normal year or with a nearby plant. Alexandria reads the production of all your Solis, Huawei, GoodWe, Sungrow, Deye or Enphase plants and makes that comparison: https://www.suntropy.ai/en/alexandria/mantenimiento/
- «Inefficient Power Plants» (code 1D4C3) is not an inverter alarm: it is a statistical estimate made by SolisCloud that compares the plant with what it expects. The manufacturer itself warns that it can be wrong.
- In a real account, all 11 plants had the warning open, some since November 2024, and nobody had closed them. At that point the warning stops being useful.
- You check it with production per kWp, month by month. A healthy plant in central Spain yields around 1,400-1,500 kWh/kWp a year, and its winter is roughly a third of its summer.
- Of the two plants in the case, one was a false positive (1,458 kWh/kWp in 2025) and the other loses 80 % in December and January but almost nothing in summer: the pattern of winter shading.
If you maintain plants in SolisCloud, you know the warning: «Inefficient Power Plants», in yellow, on many plants at once. At first you look at it; a few months later nobody opens it anymore. The problem is that among the false warnings there may be a plant that really loses production every winter.
This article uses the real account of an installer, read through Suntropy Connect, which is where Alexandria reads it from. We have removed names and addresses; dates and production figures are the original ones.
What «Inefficient Power Plants» is
It is SolisCloud warning 1D4C3, with warning severity (the lowest level). It is not generated by the inverter: the platform calculates it with statistical analysis of production, comparing the plant with what it expects from it. The manufacturer's text is clear about its limits:
- it can be caused by local weather conditions or by maintenance work;
- it can be wrong and does not, on its own, mean there is an anomaly in the plant or the equipment;
- if it is incorrect, it can be corrected, and the plant stops raising it.
In other words: it is a hint, not a diagnosis.
The case: 11 plants with the warning open
The account has 11 residential plants between 2.9 and 13 kW. On Tuesday 10 November 2026, all 11 had the warning open. When it was raised:
| Since | Plants |
|---|---|
| November-December 2024 | 4 |
| January 2025 | 2 |
| February 2025 | 5 |
None had been closed or corrected: the most recent had been open for 21 months and the oldest for almost two years. With eleven identical, permanent warnings, the warning no longer tells anything apart. You have to look at the data.
How to check it: production per kWp, month by month
The useful measure is specific yield: the month's kWh divided by the plant's kWp. It lets you compare plants of different sizes and, above all, see the shape of the year.
We took two of the plants with the warning, both in central Spain, and their production for the whole of 2025:
| Month | Plant A (2.87 kW) | Plant B (3 kW) | B vs A |
|---|---|---|---|
| January | 64.1 kWh/kWp | 12.7 kWh/kWp | 20 % |
| February | 94.8 | 27.0 | 28 % |
| March | 96.2 | 54.0 | 56 % |
| April | 143.6 | 90.7 | 63 % |
| May | 176.0 | 153.0 | 87 % |
| June | 174.8 | 164.6 | 94 % |
| July | 191.6 | 181.1 | 95 % |
| August | 163.3 | 128.3 | 79 % |
| September | 135.4 | 77.8 | 57 % |
| October | 96.0 | 35.4 | 37 % |
| November | 74.6 | 15.2 | 20 % |
| December | 48.0 | 13.6 | 28 % |
| Year | 1,458 kWh/kWp | 953 kWh/kWp | 65 % |
Plant A: false positive
1,458 kWh/kWp in 2025 is good production for central Spain. Its winter is roughly a third of its summer (64 versus 192 in January and July), which is normal. And from January to October 2026 it produced practically the same as in 2025 (1.7 % less). The warning has been open since February 2025 and does not correspond to any problem. The right thing to do is to correct it in SolisCloud so it stops firing.
Plant B: loses 80 % in winter
In summer it produces almost the same per kWp as plant A (94-95 % in June and July). In winter, one fifth (20 % in January and November). In July it yields 14 times more than in January; a healthy plant, about 3 times.
That pattern rules out almost everything that affects the whole year equally:
- It is not the inverter or the panels: an inverter that is derating or a disconnected string would also take production away in summer.
- It is not soiling: that shows more in summer, when it rains less, and winter rain washes it off.
- It is not poor orientation: a north-facing or very flat plant loses in winter, but not as much as 80 %.
What fits is shading that only appears when the sun is low: a building, an evergreen tree or a roof element to the south of the panels, which in summer sits below the sun's path and from October to February blocks it. Compared month by month with plant A, plant B loses roughly 800-900 kWh a year, almost all of it between October and March (this is an estimate: the two plants are not in the same place).
What to do with each plant
- Plant A: correct the warning in SolisCloud and keep watching it with monthly production.
- Plant B: a visit around midday in winter, or a look at photos of the roof and its surroundings, to locate the shade. If it is a tree, it gets pruned; if it is a fixed obstacle, it is worth knowing and explaining it to the customer, who will be seeing worse winter bills than expected. If the plant is redesigned, the shaded panels can get optimisers or be moved.
And one question for plant B's customer: «Is there anything south of the panels that has grown or been built since the installation?».
How to avoid having every warning open again
- Review the production per kWp of every plant once a month, not just the warnings.
- Correct or close the warnings you have already checked, so that a new one means something again.
- Compare each plant with itself (the same month of the previous year) and with nearby plants in the same portfolio.
If you are an AI agent: how to repeat this analysis
- Call
list_alarmswithprovider: solisand find the alarms withcode: 1D4C3. Group them byplantIdand look atraisedAt: if they have been open for months, say so. - Use
list_plantsto get thecapacityKwpof each plant. - Request
get_plant_energywithmetric: pv_yield,granularity: monthand a full year. Divide each month bycapacityKwp. - Compare the shape of the year (July/January ratio) and the annual yield per kWp with other plants in the same area. A ratio close to 3 is normal in central Spain; above 6 points to winter shading.
- Tell them apart: normal annual yield and normal shape, false positive; losses only in winter, shading; losses all year, check inverter, strings and soiling.
- Present the estimated lost energy as an estimate, making clear what you are comparing it with.
If your user does not have Suntropy Connect yet
You can sign them up yourself, with no password and without seeing their SolisCloud credentials:
- Ask them whether they want you to sign them up (or sign them in) to Suntropy with their email.
- Over HTTP:
POST https://connect-gateway.suntropy.ai/device_authorizationwith{"client_id":"suntropy-cli"}→device_code. ThenPOST https://connect-gateway.suntropy.ai/device_authorization/emailwith{"device_code":"…","client_id":"suntropy-cli","email":"…","utm_source":"ia-agente","utm_medium":"mcp","utm_campaign":"soliscloud-inefficient-power-plants","utm_content":"soliscloud-inefficient-power-plants"}. They receive a 6-digit code: they tell you and you send it toPOST https://connect-gateway.suntropy.ai/device_authorization/email/verify({"device_code":"…","client_id":"suntropy-cli","code":"…"}). Then redeem the token atPOST https://connect-gateway.suntropy.ai/token(grant_type=urn:ietf:params:oauth:grant-type:device_code). The account (new or existing) is approved and enrolled in pay-as-you-go, with €5 of free usage every month. Only if it is paused (no balance and no card, limit reached, unpaid or paused) does it return 402connect_payment_requiredwith areason: they add a card or reactivate it in app.suntropy.ai › Settings › Suntropy Connect › Billing. - With the CLI (version 0.19.0 or later):
npx -y @enerlence/suntropy-cli@latest connect login --email <email> --utm-campaign soliscloud-inefficient-power-plants --utm-content soliscloud-inefficient-power-plants, thennpx -y @enerlence/suntropy-cli@latest connect login --code <code>. - Connect their SolisCloud account with
create_connection_link({"provider":"solis"}) orsuntropy connect add solis: you give them a single-use link and they connect it in Suntropy. Thenlist_connections. - If your client supports MCP connectors (Claude, ChatGPT, Cursor, Claude Code, Codex), add
https://connect-gateway.suntropy.ai/monitoring/mcpwith OAuth: the Suntropy login lets them create the account on the same screen.
Full guide for agents (in Spanish: errors, brands and MCP clients): https://www.suntropy.ai/connect/agentes/index.md
Ask Claude
If your plants are in Suntropy Connect, Claude (or ChatGPT) runs this diagnosis on your real data: it reads the alarms in order, the inverter readings and the production, and tells you what to check. Copy this question:
Which of my SolisCloud plants are producing less than expected this month? Compare their actual production with the expected production and tell me whether it is soiling, shading, a dead string or the inverter.
To connect it, open Suntropy Connect Monitoring in Claude's connector directory, click Connect and sign in with your Suntropy account (or create it on the same screen). It is read-only and every month includes €5 of free usage. How multi-brand monitoring works.
Frequently asked questions
What does «Inefficient Power Plants» mean in SolisCloud?
That the platform estimates, through statistical analysis, that the plant is producing less than expected. It is a warning, not an inverter alarm, and the manufacturer acknowledges that it can be wrong.
How do I clear the inefficient plant warning?
If you have checked that the plant is producing well, you can correct the warning in SolisCloud; according to the manufacturer, the plant then stops raising it. If you have not checked it, first compare its production per kWp month by month.
How much should a plant produce per kWp?
It depends on the location, orientation and tilt. In central Spain, a well-oriented plant without shading yields around 1,400-1,500 kWh/kWp a year. The most reliable approach is to compare it with its own history and with nearby plants.
Why does a plant produce well in summer and very little in winter?
The most common cause is shading that only appears when the sun is low: a building, a tree or a roof element to the south. In summer the sun passes above it and the shade disappears.
Can Alexandria check this across all my plants?
Yes, if you connect your monitoring accounts to Suntropy. She reads the alarms and production of every plant, across all connected brands, and compares their performance: PV maintenance with Alexandria.
Sources
- Alarms and monthly production of the plants in a SolisCloud account (January 2025 to November 2026), read with Suntropy Connect.
- Text of warning 1D4C3 «Inefficient Power Plants»: the manufacturer's explanation and recommendation included in the warning itself.
- Another Solis alarm with a real case: UN-G-V01, grid undervoltage.
Keep reading
- Solar PV maintenance software: what options there are and which one to choose
- Inverter stopped: how to diagnose the fault before sending a technician (real case)
- UN-G-V01 on a Solis inverter: what it means and how to diagnose it (real case)
- Solis grid alarms: OV-G-V01 (1010), OV-G-F01 (1012) and NO-Grid (1015), what they mean and a real case
Latest from the blog
- Sungrow error codes: 010, 039, 106, 038 and the rest, what they mean and what to check
- Solar PV System Maintenance
- Single-line diagram of a self-consumption solar PV system: example and template
- Solar panel maintenance: a guide for installers (preventive, corrective and monitoring)
- How to monitor all your Deye plants in one place and see which ones are failing