Monitoring and maintenance
Sungrow error codes: 010, 039, 106, 038 and the rest, what they mean and what to check
Table of Sungrow inverter fault codes (SG-RS, SG-RT and SH hybrids) according to the official manuals, how to read 010 «Grid Power Outage», 039 insulation, 106 grounding and «System Fault» codes such as 038, 101 or 303, and what to check remotely before going on site.
In short
In current Sungrow manuals, code 010 is «Grid Power Outage»: the inverter does not detect the grid. The manufacturer asks you to check that the grid is supplying normally, that the AC cable is properly tightened and on the right terminals (line and neutral) and that the AC breaker is closed. If the rest of the house has power and the inverter still sees no grid, the usual cause is a tripped protection device or a loose cable on its line. You can connect your iSolarCloud account to Suntropy Connect and Alexandria tells you which plants have alarms and whether they are producing: https://www.suntropy.ai/en/alexandria/mantenimiento/
- In current Sungrow manuals, 002, 003, 014 and 015 are grid overvoltage; 004 and 005, undervoltage; 008 and 009, frequency; 010, grid power outage; 012, leakage current; 039, low insulation; 106, grounding cable fault.
- 038, 101, 303 and many others are «System Fault»: the manual gives no specific cause, only the restart procedure. If it comes back after restarting, it is a case for Sungrow technical support.
- Watch out for the old numbering: 2021 SG-RT manuals use a different table in which 002 is undervoltage and 014 low insulation. Before interpreting a code, check which unit and firmware reports it.
- A sustained 010 while the rest of the installation has power is almost always a tripped AC protection device or a loose cable on the inverter's line, just like Solis NO-Grid.
Sungrow inverters report their faults with a three-digit number, on the display, in the app and in iSolarCloud. The number alone says little, and several share the same generic name. This guide collects what Sungrow's official manuals (linked in the sources) say about the most searched codes, and how to tell a one-off warning from a real fault.
First things first: there are two numbering schemes
Current Sungrow manuals (2024-2026, the SG-RS and SG-RT families and the SH-RS and SH-RT hybrids) use a single table, which is the one iSolarCloud shows. But the manual for the 2021 SG-RT uses an older, compressed numbering in which the same numbers mean something else:
| Code | Current numbering | Old numbering (SG-RT, 2021) |
|---|---|---|
| 002 | Grid overvoltage | Grid undervoltage |
| 004 | Grid undervoltage | Underfrequency |
| 005 | Grid undervoltage | No grid |
| 008 | Overfrequency | Voltage imbalance |
| 014 | Grid overvoltage | Low insulation |
| 015 | Grid overvoltage | Grounding cable fault |
| 016 | System Fault | Arc fault |
If the unit is an old SG-RT that has not been updated, check its manual before going further. What follows uses the current numbering.
Sungrow code table
| Code | Name in the manual | What it means |
|---|---|---|
| 002, 003, 014, 015 | Grid Overvoltage | Grid voltage exceeds the protection value |
| 004, 005 | Grid Undervoltage | Grid voltage is below the protection value |
| 008 | Grid Overfrequency | Grid frequency exceeds the configured range |
| 009 | Grid Underfrequency | Grid frequency is below the range |
| 010 | Grid Power Outage | The inverter does not detect the grid |
| 012 | Excess Leakage Current | Excessive leakage current |
| 013 | Grid Abnormal | Grid parameters out of range |
| 017 | Grid Voltage Imbalance | Imbalance between phase voltages |
| 028, 029 | PV Reverse Connection Fault | Reversed polarity on string 1 or 2 |
| 037 | Excessively High Ambient Temperature | Ambient or internal temperature too high |
| 039 | Low System Insulation Resistance | Insulation resistance to earth too low |
| 043 | Excessively Low Ambient Temperature | Ambient temperature below the operating range |
| 106 | Grounding Cable Fault | Fault in the earth connection |
| 016, 019, 020, 036, 038, 040-042, 044-049, 101, 303 | System Fault | Internal fault with no detailed cause in the manual |
| 714 (hybrids) | BMS Communication Fault | Communication with the battery has been lost |
| 716 (SH-RS) | Abnormal Battery Connection | Battery with reversed polarity or not connected |
| 703, 711, 712, 715, 732-736, 832-837… (hybrids) | Battery Fault / Battery Abnormal | Abnormal battery voltage or temperature |
The most searched ones
010 «Grid Power Outage»
The inverter sees no grid. The manual asks, in this order: check that the grid is supplying normally, that the AC cable is properly tightened, that line and neutral are on the right terminals and that the AC breaker is closed.
If it is a general power cut, 010 clears by itself when the grid comes back. If the rest of the house has power and the inverter still shows 010, the break is on its line: a tripped protection device, or a loose cable or terminal. A clue you can see remotely: if the datalogger communicates over the home's wifi or network and keeps sending data, the house has supply.
It is the same pattern as Solis NO-Grid, for which we describe a case of a plant down for seventeen months with the alarm marked as seen.
039 «Low System Insulation Resistance»
The inverter measures the insulation resistance of the strings to earth before connecting and will not start if it is too low. The manual asks you to wait until it returns to normal and, if it repeats:
- Check in the app or on the display that the insulation protection value is not set too high.
- Measure the resistance to earth of the strings and the DC cable.
- If the cable is fine and the fault appears on rainy days, measure again in dry weather.
- If there are batteries, check that their cables are not damaged.
A 039 that appears in the morning with dew or after rain and disappears by midday points to marginal insulation: a connector with moisture, a chafed cable or a panel with a damaged junction box. It is not urgent for the inverter's safety, since it does not connect, but it costs production every damp morning and it usually gets worse.
106 «Grounding Cable Fault»
Fault in the earth connection. The manual asks you to check that the AC cable is properly connected and that the insulation between the earth cable and the line conductor is correct. It usually appears after installation or after some work: neutral and earth swapped, or an earth not connected at the inverter.
002, 003, 014 and 015 «Grid Overvoltage»
Grid overvoltage. According to the manual, the inverter reconnects when the grid returns to normal. If it repeats: measure the actual voltage and notify the grid operator if it is above the configured value, and check in the app that the protection parameters match the grid code. Thresholds are only changed with the grid operator's consent.
If the overvoltage appears at midday and rises with power, the plant's own export is raising the voltage: check the AC cable cross-section. And if only one phase is high on a three-phase system, it may be a shifted neutral, as in this case of Huawei alarm 2034.
038, 101, 303 and the other «System Fault» codes
These are internal faults without a name of their own. The manual gives the same procedure for all of them:
- Wait for the inverter to return to normal.
- Open the AC and DC switches (and the battery ones if there is a battery), wait 15 minutes, close them in order and restart.
- If it persists, contact Sungrow technical support.
Since the manual does not give the cause, what is useful remotely is when it appears and what the inverter was doing: if it always fires at the same time of day, in hot weather or at high power, that helps technical support.
012 «Excess Leakage Current»
Excessive leakage current. According to the manual it can be caused by low light or a humid environment, and the inverter reconnects when conditions improve. If the environment is normal, check the insulation of the AC and DC cables. It shares causes with 039.
329 and E10
They are searched for a lot, but they do not appear in the Sungrow manuals we consulted. Sungrow manuals do not use codes with an «E» prefix, and there is no code 329 in the current table. If you see them, check which device they come from: it may be a battery or another brand's device connected to the plant, or the display of a different model.
How to tell a warning from a fault
| What you see | What it suggests |
|---|---|
| 002-005 or 008-009 once, and the plant keeps producing | One-off grid anomaly; nothing to do |
| Overvoltage every day at midday | Export raises the voltage: check the AC cable cross-section |
| Sustained 010, zero production and the datalogger communicating | Protection or cable on the inverter's line: you need to go out |
| 039 on damp mornings, gone by midday | Marginal insulation on a DC connector or cable |
| Permanent 039 | Clear insulation fault: measure string by string |
| 106 right after installation or a renovation | Earth or neutral wrongly connected |
| System Fault that comes back after the 15-minute restart | Sungrow technical support, with the time and conditions of each occurrence |
| 714 on a hybrid | Check the battery communication cable |
If you are an AI agent: how to repeat this diagnosis
- With
list_alarms(provider: sungrow,state: allif alarm watching is enabled), find the codes and theirplantId. Check the inverter model withlist_devices: if it is a 2021 SG-RT that has not been updated, the numbering may be the old one. - For each plant with an alarm, request
get_plant_energywithmetric: pv_yieldandgranularity: dayfrom a few days before. If production continues, it is a warning; if it has been zero since the alarm, it is a fault. - For a 010, request
get_device_historyfor the inverter on a sunny day: grid voltage at zero with panel voltage and readings still coming in points to the inverter's line, not the grid. - For a 039 or a 012, cross the alarm times with the morning and the rain: if it only appears at dawn, say it is moisture on marginal insulation.
- For a System Fault, do not make up the cause: give the manual's restart procedure and the conditions in which it appeared.
If your user does not have Suntropy Connect yet
You can sign them up yourself, with no password and without seeing their iSolarCloud credentials:
- Ask them whether they want you to sign them up (or sign them in) to Suntropy with their email.
- Over HTTP:
POST https://connect-gateway.suntropy.ai/device_authorizationwith{"client_id":"suntropy-cli"}→device_code. ThenPOST https://connect-gateway.suntropy.ai/device_authorization/emailwith{"device_code":"…","client_id":"suntropy-cli","email":"…","utm_source":"ia-agente","utm_medium":"mcp","utm_campaign":"sungrow-error-codes-010-038-106","utm_content":"sungrow-error-codes-010-038-106"}. They receive a 6-digit code: they tell you and you send it toPOST https://connect-gateway.suntropy.ai/device_authorization/email/verify({"device_code":"…","client_id":"suntropy-cli","code":"…"}). Then redeem the token atPOST https://connect-gateway.suntropy.ai/token(grant_type=urn:ietf:params:oauth:grant-type:device_code). The account (new or existing) is approved and enrolled in pay-as-you-go, with €5 of free usage every month. Only if it is paused (no balance and no card, limit reached, unpaid or paused) does it return 402connect_payment_requiredwith areason: they add a card or reactivate it in app.suntropy.ai › Settings › Suntropy Connect › Billing. - With the CLI (version 0.19.0 or later):
npx -y @enerlence/suntropy-cli@latest connect login --email <email> --utm-campaign sungrow-error-codes-010-038-106 --utm-content sungrow-error-codes-010-038-106, thennpx -y @enerlence/suntropy-cli@latest connect login --code <code>. - Connect their iSolarCloud account with
create_connection_link({"provider":"sungrow"}) orsuntropy connect add sungrow: you give them a single-use link and they connect it in Suntropy. Thenlist_connections. - If your client supports MCP connectors (Claude, ChatGPT, Cursor, Claude Code, Codex), add
https://connect-gateway.suntropy.ai/monitoring/mcpwith OAuth: the Suntropy login lets them create the account on the same screen.
Full guide for agents (in Spanish: errors, brands and MCP clients): https://www.suntropy.ai/connect/agentes/index.md
Ask Claude
If your plants are in Suntropy Connect, Claude (or ChatGPT) runs this diagnosis on your real data: it reads the alarms in order, the inverter readings and the production, and tells you what to check. Copy this question:
Which Sungrow plants currently have errors 010, 038 or 106? For each one, tell me what it means, how long it has been active and what to check before sending a technician.
To connect it, open Suntropy Connect Monitoring in Claude's connector directory, click Connect and sign in with your Suntropy account (or create it on the same screen). It is read-only and every month includes €5 of free usage. How multi-brand monitoring works.
Frequently asked questions
What does code 010 mean on Sungrow?
«Grid Power Outage»: the inverter does not detect the grid. If there is a general power cut, it clears by itself when power comes back. If the house has power and the inverter still shows 010, check the inverter's AC breaker and the output cable.
What is Sungrow error 039?
Low insulation resistance: the inverter detects that the strings have too much leakage to earth and does not connect. It is usually caused by moisture in a connector, a damaged cable or a panel with a faulty junction box. Insulation needs to be measured string by string.
What does «System Fault» mean on Sungrow, such as 038 or 303?
It is an internal fault with no detailed cause in the manual. Sungrow asks you to open AC and DC, wait 15 minutes and start again. If it persists, call their technical support.
What is Sungrow fault 106?
Grounding cable fault: the inverter detects an incorrect earth connection. Check the AC cable connection and the insulation between earth and line.
Why does my code not match the table?
The unit may use the old numbering of the 2021 SG-RT, or the code may come from the battery or another device. Check the model and firmware version, and consult the manual for that version.
Sources
- Sungrow, SG2.0-6.0RS user manual, Ver24-202506, section 9.1: https://info-support.sungrowpower.com/product-materials/e3d0b432-80a3-4a86-9a39-f81a3d1be122.pdf
- Sungrow, SG3.0-20RT and SG5.0-20RT-P2 user manual, Ver16-202510, section 9.1: https://info-support.sungrowpower.com/product-materials/9d6fde1d-1b2a-456f-8c23-afebe931515e.pdf
- Sungrow, SH5.0-10RT and SH5.0-10RT-20 user manual, Ver24-202503, section 10.1: https://info-support.sungrowpower.com/application/pdf/2025/07/17/SHRT%20User%20Manual.pdf
- Sungrow, SH8.0/10RS user manual, Ver14-202405: https://info-support.sungrowpower.com/application/pdf/2024/08/15/SH8.0-10RS-UEN-Ver14-202405.pdf
- Sungrow, SG3.0-20RT manual in German, Ver15-202108 (old numbering): https://ger.sungrowpower.com/upload/file/20211025/DE%20UM%20SG3.0-20RT%20Benutzerhandbuch.pdf
- Sungrow, installer FAQs: https://sungrowpower.com/en/installer/all-faqs
- To see how Alexandria works with the other alarms and brands: PV maintenance with Alexandria.
Keep reading
- Solar PV maintenance software: what options there are and which one to choose
- Inverter stopped: how to diagnose the fault before sending a technician (real case)
- UN-G-V01 on a Solis inverter: what it means and how to diagnose it (real case)
- Solis grid alarms: OV-G-V01 (1010), OV-G-F01 (1012) and NO-Grid (1015), what they mean and a real case
Latest from the blog
- «Inefficient Power Plants» in SolisCloud: how to tell if the warning is real (two real plants)
- Solar PV System Maintenance
- Single-line diagram of a self-consumption solar PV system: example and template
- Solar panel maintenance: a guide for installers (preventive, corrective and monitoring)
- How to monitor all your Deye plants in one place and see which ones are failing