# Solis grid alarms: OV-G-V01 (1010), OV-G-F01 (1012) and NO-Grid (1015), what they mean and a real case

> What the grid alarms on Solis inverters and their codes mean (1010 OV-G-V, 1012 OV-G-F, 1013 UN-G-F, 1015 NO-Grid), how to tell an out-of-range grid from a missing grid, and a real case of a 3.4 kW plant that has been down for seventeen months with the NO-Grid alarm marked as seen.

- URL: https://www.suntropy.ai/en/blog/solis-grid-alarms-ov-g-v01-no-grid/
- Published: 2026-11-26 · Updated: 2026-11-26
- Publisher: Suntropy (AI software for solar installers, https://www.suntropy.ai)

## Short answer

**What does the NO-Grid alarm on a Solis inverter mean?**

NO-Grid (code 1015 in SolisCloud) means the inverter does not detect the AC grid at its output and cannot connect. Unlike OV-G-V or UN-G-V, which warn of an out-of-range grid, NO-Grid usually means something is interrupting the AC between the consumer unit and the inverter (a tripped MCB or RCD, a loose cable or terminal). If the datalogger is still communicating, the house has power and the break is on the inverter's line. You can connect your SolisCloud plants to Suntropy Connect and Alexandria tells you which plants have not produced for days and why: https://www.suntropy.ai/en/alexandria/mantenimiento/

## In short

- Solis grid alarms come in two kinds. **OV-G-V, UN-G-V, OV-G-F and UN-G-F** say the grid is **out of range** (voltage or frequency). **NO-Grid** says the inverter **sees no grid at all**.
- Out-of-range alarms are usually one-offs and the inverter reconnects by itself. **A sustained NO-Grid does not clear by itself**: it is almost always a tripped AC protection device or a loose cable between the consumer unit and the inverter.
- In the real case, a **3.36 kWp** plant went from **18-20 kWh a day to zero** on 1 June 2025. Seventeen months later it is still down, with the alarm **marked as seen** in the portal. About **6,000 kWh** have been lost.
- The clue that solves it remotely: the wifi datalogger **keeps sending readings**. If the router has power, the house has power: the break is on the inverter's line, not on the grid.

In SolisCloud, grid alarms are the most frequent ones and the first ones you learn to ignore. They are almost always a grid spike or dip, and the inverter reconnects by itself within a few minutes. But there is one that **does not clear by itself**, and in the portal it looks just as harmless as the others: **NO-Grid**.

> Looking for Solis **error 1011 (UN-G-V01)**? Grid undervoltage has its own diagnosis, with a real case, in **[Solis error 1011 (UN-G-V01)](/en/blog/solis-un-g-v01-grid-undervoltage/)**.

This article explains what each alarm in the grid family means and uses a **real case**: a home in the province of Ciudad Real (Spain) with **3.36 kWp** and a single-phase **Solis S6-GR1P3K** inverter, down since **1 June 2025**. The data come from SolisCloud, read through **Suntropy Connect**, which is where **Alexandria** gets them. We removed the name and address; production, times and readings are the original ones.

> The plant in this case is on a European **230 V, 50 Hz** grid. In North America the nominal values differ (60 Hz; 120/240 V split-phase or 208/480 V three-phase), but the alarms and the diagnostic reasoning are the same.

## Solis grid alarms and their codes (1010 to 1019)

According to Solis's official code list and its inverter manuals (linked in the sources):

| Alarm | Code | What it means according to Solis |
|---|---|---|
| **OV-G-V01** | 1010 | Grid voltage exceeds the first overvoltage threshold of the grid code for the configured time |
| OV-G-V02 | 1010 | Instantaneous grid voltage above 1.35 times the nominal peak voltage |
| OV-G-V03 | 1010 | Voltage exceeds the grid code's 10-minute overvoltage limit |
| OV-G-V04 | 1010 | Voltage exceeds the second overvoltage threshold for the configured time |
| **UN-G-V01 / 02** | 1011 | Grid voltage below the threshold |
| **OV-G-F01 / 02** | 1012 | Grid frequency above the first or second grid code threshold |
| UN-G-F01 / 02 | 1013 | Grid frequency below the threshold |
| **NO-Grid** | 1015 | The inverter detects no grid voltage |
| G-PHASE | 1016 | Unbalanced three-phase grid |
| OV-G-I | 1018 | Grid output overcurrent |
| IGFOL-F | 1019 | Grid current tracking error |
| GRID-INTF | 1030 | Grid interference: non-ideal voltage waveform |

Variants 01 to 05 of the same alarm share a code and are told apart by a sub-code. We have seen codes 1011 and 1015 exactly as such in SolisCloud alarms.

What the manufacturer recommends:

- **OV-G-V and UN-G-V:** if it happens in isolation, it is a brief grid anomaly and the inverter resumes operation by itself. If it repeats, check that the grid standard is set correctly, measure voltage and frequency, and check the AC breaker and cable. The manuals add that an AC cable with too much resistance causes overvoltage and that the fix is a larger cross-section. Only adjust the thresholds with the grid operator's approval.
- **OV-G-F and UN-G-F:** only adjust the protection limits if the grid operator allows it.
- **NO-Grid:** check the connections and the grid breaker, and measure the grid voltage at the inverter terminals.
- **GRID-INTF:** may be caused by several inverters on the same line with a non-ideal voltage waveform; restart the inverter, adjust the grid filter in the special settings or check the downstream equipment.

The difference that matters is between the first rows and the last one:

- **Out-of-range alarms (OV-G-V, UN-G-V, OV-G-F, UN-G-F)** say there is a grid, but voltage or frequency have left the grid code window. The inverter disconnects for protection and comes back when the grid returns to normal. In isolation they are not a fault.
- **NO-Grid** says the inverter **sees no grid**: voltage and frequency at zero at its output. If it lasts longer than a power cut, something is open between the grid and the inverter, and it will not close by itself.

### OV-G-V01 (1010): grid overvoltage

The inverter measured a grid voltage above the grid code's first overvoltage threshold for the configured time and stops exporting until it drops. In isolation, it is the grid. If it repeats around midday, when the inverter exports the most, suspect the line: a long or undersized AC cable raises the voltage at the inverter terminals above that at the consumer unit, and the fix given in the manuals is a larger cross-section. Before thinking about thresholds, measure the voltage at the consumer unit and at the terminals while the inverter is producing.

### OV-G-F01 (1012): grid overfrequency

The frequency exceeded the grid code threshold. It is almost always a grid event and the inverter reconnects by itself. If it repeats, check that the grid standard configured on the inverter is the right one for the country (a wrong standard leaves thresholds that do not apply). Limits are only changed with the grid operator's permission.

### NO-Grid (1015): the inverter sees no grid

This is not an out-of-range grid: it is a **missing** grid at the inverter output. If it lasts longer than a power cut, something is open between the consumer unit and the inverter. It is the one that costs the most money, and it is the one in this article's case.

Looking for **UN-G-V01** (1011, undervoltage)? It has its own diagnosis, with another real case, in [UN-G-V01 on Solis](/en/blog/solis-un-g-v01-grid-undervoltage/).

## The case: from 19 kWh a day to zero, for seventeen months

The plant's daily production at the end of May 2025, in kWh:

| Day | Production |
|---|---|
| 27 May | 19.3 |
| 28 May | 18.8 |
| 29 May | 18.8 |
| 30 May | 18.0 |
| 31 May | 18.1 |
| **1 June** | **0** |
| Since then | **0** |

There is no prior degradation: the plant produced normally until Saturday the 31st, and on Sunday 1 June at **7:05**, waking up with the first sun, the inverter raised **NO-Grid (1015)** and never connected again.

Monthly production makes it clear:

| Month | 2024 | 2025 | 2026 |
|---|---|---|---|
| May | 590 | 525 | 0 |
| June | 507 | **0** | 0 |
| July | 578 | 0 | 0 |
| August | 487 | 0 | 0 |
| September | 347 | 0 | 0 |
| October | 214 | 0 | 0 |

Taking 2024 production and the good months of 2025 as a reference, since 1 June 2025 the plant has failed to produce **about 6,000 kWh**: more than a whole year of production.

The most striking part is in the portal: the alarm shows the status **«acknowledged»**. Someone saw it, marked it as read, and the plant stayed down.

## What today's readings say

These are the inverter readings on the morning of 10 November 2026, every five minutes:

| Time | Status | PV input 1 | PV input 2 | PV current | Grid voltage | Frequency | Power |
|---|---|---|---|---|---|---|---|
| 08:29 | on | 123.7 V | 124.0 V | 0 A | **0 V** | **0 Hz** | 0 kW |
| 10:09 | on | 134.0 V | 134.3 V | 0 A | **0 V** | **0 Hz** | 0 kW |
| 11:44 | on | 135.1 V | 135.3 V | 0 A | **0 V** | **0 Hz** | 0 kW |

Three things:

**1. The inverter is alive.** It has panel voltage on both inputs, measures its temperature (17-19 °C) and sends readings every five minutes. The electronics work and the DC side supplies voltage.

**2. It sees no grid at all.** AC voltage **0 V** and frequency **0 Hz**. It is not a high grid, a low grid or an unstable grid: there is no grid at its output. That is why the panel current is zero: without a grid it cannot export.

**3. The datalogger is wifi and keeps communicating.** That means the **home's router has power**, so the house has supply. The grid reaches the consumer unit; what is missing is the stretch **from the consumer unit to the inverter**.

## Diagnosis

With those three clues, the hypotheses from most to least likely:

1. **Tripped AC protection on the PV circuit** (the MCB or RCD on the inverter's line). This is the most frequent: a storm, a one-off insulation fault or a sympathetic trip, and nobody resets it because the house still has power.
2. **Loose or burnt AC cable or terminal** at the inverter's output connector or in the protection board.
3. **Inverter AC switch or isolator left open**, for example after work on the installation.
4. **Fault in the inverter's own relay or grid measurement.** Only considered if there are 230 V at the output terminal and the inverter still reports 0 V.

What it is **not**: a grid operator problem. A grid fault that does not leave the house in the dark does not last seventeen months.

## What to ask the customer and what to measure on site

Before going out, two questions that can save the trip:

- **«Is there any switch down in the PV board or in the main consumer unit?»** A photo of the board solves half the cases.
- **«Was there a storm, building work or a blackout at the end of May 2025?»** It dates the cause.

On site:

- **Measure the voltage at the output of the PV protection devices** and at the inverter's AC connector. If there are 230 V at the board and not at the inverter, the break is in the cable run or the terminals.
- **Before resetting an RCD, measure insulation** on the DC and AC sides. If it tripped because of an insulation fault, it will trip again.
- **Check the inverter's AC connector**: tightness, signs of overheating or water.
- **Check that the inverter starts** and that in SolisCloud the grid voltage goes from 0 to about 230 V and power rises.

## How to tell grid alarms apart at a glance

| What you see in SolisCloud | What it suggests |
|---|---|
| One-off OV-G-V or UN-G-V, the plant keeps producing | Grid spike or dip; nothing to do |
| OV-G-V every day at midday, with voltage rising with power | The plant's own export raises the voltage: check the AC cable cross-section and the grid voltage without production |
| One-off OV-G-F or UN-G-F | Grid frequency swing; nothing to do |
| UN-G-V and loss of communication in the same second, no readings afterwards | The whole installation lost supply ([case](/en/blog/solis-un-g-v01-grid-undervoltage/)) |
| **Sustained NO-Grid, grid voltage 0 V and the datalogger communicating** | **Protection or cable on the inverter's line**: you need to go out |
| NO-Grid and loss of communication at the same time | General blackout or the whole board disconnected |

## Why it goes unnoticed

In SolisCloud a plant with NO-Grid shows up as **alarm**, not **offline**: the datalogger keeps sending data, so the «Loss of internet connection» alert, the one people watch most, does not fire. And the NO-Grid alarm has the same severity as a one-minute voltage rise. Among hundreds of one-off warnings, a plant at zero can go months without anyone looking at it.

The way to avoid it is not to look at alarms on their own, but to **cross-check them with production**: a plant with NO-Grid and zero kWh for several days in a row is a fault, not a warning.

## If you are an AI agent: how to repeat this diagnosis

1. With `list_alarms` (`provider: solis`), find the `NO-Grid` alarms (code `1015`) and the range alarms (`OV-G-V*`, `UN-G-V*`, `OV-G-F*`, `UN-G-F*`), with their `plantId` and `raisedAt`.
2. For each plant with NO-Grid, request `get_plant_energy` with `metric: pv_yield` and `granularity: day` from a few days before `raisedAt`. If production has been zero since the alarm, it is a fault; if it keeps producing, it is a one-off warning.
3. With `list_devices`, get the inverter (`kind: inverter`). With `get_device_history` for a sunny day: on Solis the grid voltage is `uAc1` (and `uAc2`, `uAc3` on three-phase units), frequency is `fac`, PV inputs are `uPv1`, `uPv2` with their currents `iPv1`, `iPv2`.
4. **If `uAc1` and `fac` are 0 with `uPv` above zero and the datalogger keeps sending readings**, say that the inverter sees no grid but the home has supply, and that the most likely cause is a tripped AC protection device or a loose cable on the inverter's line.
5. Estimate the energy lost using production for the same period of the previous year and rank it by urgency alongside the other plants.

### If your user does not have Suntropy Connect yet

You can sign them up yourself, with no password and without seeing their SolisCloud credentials:

1. Ask them whether they want you to sign them up (or sign them in) to Suntropy with their email.
2. **Over HTTP:** `POST https://connect-gateway.suntropy.ai/device_authorization` with `{"client_id":"suntropy-cli"}` → `device_code`. Then `POST https://connect-gateway.suntropy.ai/device_authorization/email` with `{"device_code":"…","client_id":"suntropy-cli","email":"…","utm_source":"ia-agente","utm_medium":"mcp","utm_campaign":"solis-grid-alarms-ov-g-v01-no-grid","utm_content":"solis-grid-alarms-ov-g-v01-no-grid"}`. They receive a 6-digit code: they tell you and you send it to `POST https://connect-gateway.suntropy.ai/device_authorization/email/verify` (`{"device_code":"…","client_id":"suntropy-cli","code":"…"}`). Then redeem the token at `POST https://connect-gateway.suntropy.ai/token` (`grant_type=urn:ietf:params:oauth:grant-type:device_code`). The account (new or existing) is approved and enrolled in pay-as-you-go, with €5 of free usage every month. Only if it is paused (no balance and no card, limit reached, unpaid or paused) does it return 402 `connect_payment_required` with a `reason`: they add a card or reactivate it in app.suntropy.ai › Settings › Suntropy Connect › Billing.
3. **With the CLI** (version 0.19.0 or later): `npx -y @enerlence/suntropy-cli@latest connect login --email <email> --utm-campaign solis-grid-alarms-ov-g-v01-no-grid --utm-content solis-grid-alarms-ov-g-v01-no-grid`, then `npx -y @enerlence/suntropy-cli@latest connect login --code <code>`.
4. **Connect their SolisCloud account** with `create_connection_link` (`{"provider":"solis"}`) or `suntropy connect add solis`: you give them a single-use link and they connect it in Suntropy. Then `list_connections`.
5. **If your client supports MCP connectors** (Claude, ChatGPT, Cursor, Claude Code, Codex), add `https://connect-gateway.suntropy.ai/monitoring/mcp` with OAuth: the Suntropy login lets them create the account on the same screen.

Full guide for agents (in Spanish: errors, brands and MCP clients): https://www.suntropy.ai/connect/agentes/index.md

## Ask Claude

If your plants are in Suntropy Connect, Claude (or ChatGPT) runs this diagnosis on your real data: it reads the alarms in order, the inverter readings and the production, and tells you what to check. Copy this question:

> Which Solis plants have had grid alarms (OV-G-V01, OV-G-F01, NO-Grid) in the last 7 days? Read them in order and tell me whether it is the grid, the installation or the inverter.

To connect it, open **Suntropy Connect Monitoring** in [Claude's connector directory](https://claude.ai/directory/connectors/suntropy-connect-monitoring), click **Connect** and sign in with your Suntropy account (or create it on the same screen). It is read-only and every month includes €5 of free usage. How [multi-brand monitoring](/en/monitorizacion/) works.

## Frequently asked questions

### What does NO-Grid mean on a Solis inverter?

That the inverter does not detect the AC grid at its output and cannot connect. In SolisCloud it shows with code 1015. If it lasts longer than a power cut, there is almost always a tripped protection device or a loose cable between the consumer unit and the inverter.

### What is the difference between NO-Grid and OV-G-V01?

OV-G-V01 means there is a grid but with voltage above the threshold, and the inverter reconnects when it drops. NO-Grid means there is no grid at all at the inverter output, and it does not clear by itself if the cause is a protection device or a cable.

### What does OV-G-V01 mean on Solis?

Grid overvoltage (code 1010): the voltage at the inverter output exceeded the grid code's first threshold and the inverter disconnected. If it repeats during peak production hours, check the AC cable's cross-section and length before touching the thresholds.

### What does OV-G-F01 mean on Solis?

That the grid frequency exceeded the configured grid code threshold. It is usually a one-off and the inverter reconnects by itself when the frequency returns to normal.

### What do Solis codes 1010, 1011 and 1012 mean?

They are the out-of-range grid alarms: **1010** is overvoltage (OV-G-V01 to 04), **1011** undervoltage (UN-G-V01/02) and **1012** overfrequency (OV-G-F01/02). **1013** is underfrequency and **1015** is NO-Grid. If they appear as one-offs, the inverter reconnects by itself. If one of them stays open for days, like a 1011 we have seen active since early October on a plant whose datalogger was also disconnected, look at production: the inverter may not have reconnected.

### Does marking the alarm as read in SolisCloud fix it?

No. Marking it as read only changes its status in the portal; the inverter stays disconnected until the cause is fixed. In this article's case the alarm was marked as seen and the plant had been down for seventeen months.

### Can I reset the PV RCD myself?

The user can reset it, but if the RCD tripped because of an insulation fault it will trip again, so an installer should measure insulation first. If it trips again, do not keep trying.

## Sources

- Production, alarms and readings from the SolisCloud platform of the installation in this case (April 2024 to 10 November 2026), read with Suntropy Connect.
- Complete list of Solis alarm codes (official Solis knowledge base, «Solis Inverter Alarm Codes (Complete List)», April 2025): https://usservice.solisinverters.com/support/solutions/articles/73000560423-solis-inverter-alarm-codes-complete-list-
- Solis, «OV-G-V Alarm» article: https://usservice.solisinverters.com/support/solutions/articles/73000560435-ov-g-v-alarm
- Solis S6-GR1P(0,7-3,6)K-M installation and operation manual, version 1.5, troubleshooting table: https://www.solisinverters.com/uploads/file/Solis_Manual_S6-GR1P(0,7-3,6)K-M_FN_EUR_V1,5(20260817).pdf
- Solis S5-GR3P(3-13)K installation and operation manual, version 1.4, table 9.1: https://www.solisinverters.com/uploads/file/Solis_Manual_S5-GR3P(3-13)K_FN_EUR_V1,4(20240702).pdf
- Solis S6-GR1P(2,5-6)K-S manual in Portuguese, table 8.1 (numeric codes with sub-code).
- To see how Alexandria works with the other alarms and brands: [PV maintenance with Alexandria](/en/alexandria/mantenimiento/).

---

Never leave a plant down for seventeen months: Connect your SolisCloud accounts and your other brands to Suntropy Connect. Alexandria cross-checks the alarms with each inverter's production and readings, tells you which ones are really down and what to check before you drive out. Read-only, with €5 of free usage every month. Free account: https://app.suntropy.ai/signup