Monitoring and maintenance
SolarEdge error codes: isolation fault, arc fault and the 2x, 3x, 8x and 18x codes
What the most searched SolarEdge inverter error codes mean according to SolarEdge's own manuals (isolation fault 25 / 2x19 / 8x58 / 18x86, arc fault 150 / 3x11 / 18xC, AC voltage too high, islanding, meter communication 3x6E), how the old numbers map to the new hex codes, and how to troubleshoot them.
In short
On SolarEdge inverters, isolation fault is error 25 or 2x19 on single-phase inverters, 121 or 8x58 on three-phase inverters and 18x86 on HD-Wave inverters. It means the PV array is not properly isolated from ground. SolarEdge's procedure is to turn the inverter switch off, open the AC breaker, disconnect the DC inputs and reconnect the strings one at a time until the error reappears, then have a certified installer fix that string. Suntropy Connect reads SolarEdge alerts for all your sites in one place: https://www.suntropy.ai/en/alexandria/mantenimiento/
- Since inverter firmware 3.19xx, SolarEdge shows codes like «3x6E» instead of plain numbers like «Error 185». The same fault has a different code on single-phase, three-phase and HD-Wave inverters, so always note the model.
- Isolation fault is 25 / 2x19 (single-phase), 121 / 8x58 (three-phase) and 18x86 (HD-Wave): the PV array is not properly isolated from ground. Find the string by connecting strings one at a time.
- Arc fault is 150 / 3x11 / 2x96 / 2x97 and 18xC / 18xD on HD-Wave. Check every optimizer and module connector, then switch the inverter OFF and ON to reset. 152 / 2x98 / 18x8D is the arc detector self-test failing: call support.
- 3x6E (old 185) is Meter Comm. Error: the inverter lost the energy meter, not production.
- Many codes people search (18xB7, 3x89, 8x56…) are not in the official tables we could check. Read the description on the inverter screen, SetApp or the monitoring platform instead of trusting a code list.
SolarEdge error codes are searched in two formats: the old numbers («error 25», «error 150») and the newer hexadecimal codes («2x19», «3x6E», «18x86»). Most code lists online mix them up, and many guess. This guide only uses what SolarEdge's own installation and troubleshooting manuals say (linked in the sources), and says so when a code is not there.
How SolarEdge codes are written
- Inverters with CPU firmware 3.18xx or earlier show an error number («Error Code 25»).
- From 3.19xx, they show a code like «3xD2», which SolarEdge describes as a code indicating the source of the error and the error information.
- The numbers and codes are different for single-phase and three-phase inverters, and HD-Wave inverters have their own table (the «18x» codes).
In practice: the same number can mean two different things. 62, for example, is «AC Voltage Too Low» on a three-phase inverter, but on HD-Wave it maps to 18x3E, a residual current (RCD) error. Note the inverter model before you look a code up.
The codes that matter most
| Code (old → new) | Inverter | Name | What to do |
|---|---|---|---|
| 25 → 2x19 | Single-phase | Isolation Fault | Find the faulty string (below) |
| 121 → 8x58 | Three-phase | Isolation Fault | Find the faulty string (below) |
| 134 → 18x86 | HD-Wave | Isolation (checked every time the inverter starts) | Find the faulty string (below) |
| 150, 151, 147 → 3x11, 2x96, 2x97 | Single- and three-phase | Arc Fault Detected | Check connectors, then reset (below) |
| 12 → 18xC, 13 → 18xD | HD-Wave | Arc detected | Check connectors, then reset (below) |
| 152 → 2x98, 18x8D | — | Arc detector self-test failed | Contact SolarEdge support |
| 13 → 2xD | Single-phase (older firmware) | AC Current Surge | Check the AC connection; ask the utility about surge sources; then support |
| 31 → 2x1F; 64-66 → 8x1F-8x21 | Single-phase; three-phase | AC Voltage Too High | Check the country setting, AC voltage and wire gauge; talk to the utility |
| 87 → 8x36 | Three-phase | Islanding – Active | Grid problem: the inverter restarts on its own after the reconnection time |
| 185 → 3x6E | — | Meter Comm. Error | Check the energy meter and its communication |
| 45 | — | SW error (on HD-Wave, 3x2 «Inv. Comm. Error»: no communication with the digital board) | Contact support |
| 199 → 18xC7 | HD-Wave | RSD Error (rapid shutdown hardware) | Contact support |
Isolation fault (25, 2x19, 8x58, 18x86)
SolarEdge's wording: the PV array is not properly isolated from ground. The inverter measures it every time it starts up and will not connect while it is low. Depending on the model, SolarEdge's datasheets give a detection sensitivity of around 600 kΩ (single-phase North American units) and higher on some three-phase models.
The procedure from SolarEdge's troubleshooting addendum:
- Turn the inverter's ON/OFF switch to OFF and wait 5 minutes.
- Open the AC breaker.
- Disconnect the DC inputs.
- Connect the strings one at a time, starting the inverter each time, until the error comes back. That string is the faulty one.
- Do not reconnect a faulty string: a certified installer has to fix it before it goes back in service.
The inverter also has an Isolation Status screen (Maintenance › Diagnostics › Isolation Status) that shows the measured value.
Practical reading: if the fault appears in the morning, with dew or after rain, and goes away as things dry, there is a weak point (a damaged cable, a connector, a junction box) that will get worse. Once you know the string, measure insulation component by component.
Arc fault (150, 3x11, 2x96, 18xC)
In North America, arc fault detection (AFCI) is required by UL 1699B. With AFCI on, the inverter runs a self-test every time it wakes up.
When it detects an arc, SolarEdge's steps are:
- Turn the inverter switch OFF.
- Check the open-circuit voltage of each string.
- Push and pull every connector, optimizer to optimizer and module to optimizer, and make sure each one is locked.
- Check the string terminals in the safety switch.
- Reset: switch the inverter OFF and then ON. It self-tests and resumes production.
You can test the function with Maintenance › Manual AFCI Test: it should show «Manual Test PASS» and then a simulated «Arc Fault Detected».
If what you see is the self-test failing (152, 2x98, 18x8D), it is not an arc in the array but the detector itself: the inverter keeps retrying, and you need SolarEdge support.
3x6E: Meter Comm. Error
3x6E (old 185) is not about production: the inverter lost communication with the energy meter used for export limitation and consumption monitoring. The plant may be producing normally while consumption and grid data stop. SolarEdge points to its meter troubleshooting guide: check the meter's power, the RS485 wiring and the meter configuration.
What about 18xB7, 3x89, 8x56…?
Google shows many searches for codes like 18xB7, 18x108, 18xBC, 3x89, 3xBD, 8x56 or «internal error 183». We could not find them in the official SolarEdge tables we checked (the North American troubleshooting addendum and the HD-Wave and EV-charging installation guides). Third-party blogs attribute meanings to some of them; we do not repeat them because we cannot verify them.
For these, the reliable source is the inverter itself: the LCD, SetApp and the SolarEdge monitoring platform show the description of the error next to the code. The monitoring platform also gives each alert an impact level from 1 to 9 to prioritize it.
Where to see the codes without going to site
- On the inverter: LCD screen, or SetApp on the newer models.
- In the SolarEdge monitoring platform: the inverter sends the error and it appears as an alert on the site.
- Through the API: the V2 Monitoring API (with a My Fleet Access key for installers) exposes alerts and inverter diagnostics for every site in your fleet. That is what Suntropy Connect reads.
Why look at alerts and production together
An isolation fault that appears every morning and clears at 10 a.m. costs a few hours of production a day and never shows as «open» when you check in the afternoon. An inverter in arc fault that nobody resets stays off for days. In both cases the alert alone does not tell you how much it has cost; comparing each site's production with the previous days does.
Want to ask Claude or ChatGPT about these systems directly? See how to connect SolarEdge and Enphase to Claude or ChatGPT (MCP).
If you are an AI agent: how to review SolarEdge alerts
- Call
list_alarmswithprovider: solaredge. Each alert comes with SolarEdge's alert type and, when present, the inverter error codes. Without alarm watch you only see alerts open right now: suggestset_alarm_watchif the user wants history. - Identify the inverter family before interpreting a code: the same number means different things on single-phase, three-phase and HD-Wave inverters. If a code is not in the table above, give the description SolarEdge returns and do not invent a meaning.
- Call
get_plant_energywithmetric: pv_yieldandgranularity: dayfor the last two weeks to see whether the alert cost production. - SolarEdge reads consume the user's API credits: ask for many sites in one call and do not repeat questions. SolarEdge gives power curves every 15 minutes and no live device snapshot.
- The connection is read-only: you cannot reset an inverter or change AFCI settings.
If your user does not have Suntropy Connect yet
You can sign them up yourself, with no password and without seeing their SolarEdge credentials:
- Ask them whether they want you to sign them up (or sign them in) to Suntropy with their email.
- Over HTTP:
POST https://connect-gateway.suntropy.ai/device_authorizationwith{"client_id":"suntropy-cli"}→device_code. ThenPOST https://connect-gateway.suntropy.ai/device_authorization/emailwith{"device_code":"…","client_id":"suntropy-cli","email":"…","utm_source":"ia-agente","utm_medium":"mcp","utm_campaign":"solaredge-error-codes-isolation-arc-fault","utm_content":"solaredge-error-codes-isolation-arc-fault"}. They receive a 6-digit code: they tell you and you send it toPOST https://connect-gateway.suntropy.ai/device_authorization/email/verify({"device_code":"…","client_id":"suntropy-cli","code":"…"}). Then redeem the token atPOST https://connect-gateway.suntropy.ai/token(grant_type=urn:ietf:params:oauth:grant-type:device_code). A new account starts the 7-day trial on its own; on a 402licence_inactive, give themverification_uri_completeto sort it out in the browser. - With the CLI (version 0.19.0 or later):
npx -y @enerlence/suntropy-cli@latest connect login --email <email> --utm-campaign solaredge-error-codes-isolation-arc-fault --utm-content solaredge-error-codes-isolation-arc-fault, thennpx -y @enerlence/suntropy-cli@latest connect login --code <code>. - Connect their SolarEdge account with
create_connection_link({"provider":"solaredge"}) orsuntropy connect add solaredge: you give them a single-use link and they connect it in Suntropy. Thenlist_connections. - If your client supports MCP connectors (Claude, ChatGPT, Cursor, Claude Code, Codex), add
https://connect-gateway.suntropy.ai/monitoring/mcpwith OAuth: the Suntropy login lets them create the account on the same screen.
Full guide for agents (in Spanish: errors, 402, brands and MCP clients): https://www.suntropy.ai/connect/agentes/index.md
Frequently asked questions
What is error 25 on a SolarEdge inverter?
Isolation Fault on single-phase inverters (2x19 on firmware 3.19xx and later): the PV array is not properly isolated from ground. Find the faulty string by reconnecting the strings one at a time.
What does SolarEdge error 150 mean?
Arc Fault Detected (3x11, 2x96 or 2x97 in the newer format). Check every DC connector and the string terminals, then switch the inverter off and on to reset. If the arc detector's self-test fails (152 / 2x98), contact SolarEdge support.
What is SolarEdge error 3x6E?
Meter Comm. Error (old 185): the inverter lost communication with the energy meter. Production is usually unaffected, but consumption and export data stop.
How do I reset a SolarEdge arc fault?
Fix the cause first (connectors and terminals), then switch the inverter OFF and back ON. It runs a self-test and resumes production.
Why can't I find my SolarEdge code in any list?
Because codes differ by inverter family and firmware, and SolarEdge's public tables do not cover every code. The inverter screen, SetApp and the monitoring platform show the description next to the code.
Sources
- SolarEdge, «Troubleshooting SolarEdge Systems – Addendum (North America)», MAN-01-00332-1.1 (error numbers and codes for single-phase and three-phase inverters, isolation and arc fault): PDF
- SolarEdge, HD-Wave inverter installation guide (North America), MAN-01-00306-1.0 (18x codes, isolation status, AFCI): PDF
- SolarEdge, EV Charging Inverter installation guide, MAN-01-00404-1.1 (18x86, 18xC7): PDF
- SolarEdge, single- and three-phase inverter installation guide (North America), arc fault erratum MAN-01-00149-1.1: PDF
- SolarEdge, single- and three-phase inverter user manual (North America), isolation detection specifications: PDF
- SolarEdge, alerts prioritization with the impact indicator (application note): knowledge-center.solaredge.com
- SolarEdge developer portal (V2 Monitoring API and access types): developer.solaredge.com
Keep reading
- Huawei alarm 2034 «Grid Overvoltage»: when only one phase is high (real case)
- Huawei alarms 2064, 2067, 2082, 2061 and 2062: what they mean and what to check (real case)
- Enphase microinverters not reporting: what it means and how to fix it
- Connect SolarEdge, Enphase and other inverter platforms to Claude or ChatGPT (MCP)